ES3000 Digital Earth Resistance Tester

ES3000 Digital Earth Resistance Tester

  • Resistance Range : 0.01Ω~3000Ω
  • Voltage Range :0.01-100V AC
  • measurement mode:Precise three-wire measurement, simple two-wire measurement
  • USB interface:With USB interface, software monitoring, storage data can be uploaded to the computer, save and print
  • Data storage:500 groups, flashing “FULL” symbol indicates that the memory is full
Grounding Resistance Range0.01Ω~3000Ω    Accuracy ±1.5%rdg±5dgt
Grounding Resistance Resolution0.01Ω
Grounding Voltage Range0.01~100.0V AC        Accuracy ±1%rdg±3dgt
Grounding Voltage Resolution0.01V
Baseline conditions23℃±5℃,below 75%rh   (Auxiliary ground resistance 100Ω ± 5%, voltage to ground <10V)
FunctionEarth resistance measurement, ground voltage measurement, low value resistance measurement 
Power8.4V lithium battery (built-in)
BacklightControllable gray screen backlight, suitable for use in dim places
measurement modePrecise three-wire measurement, simple two-wire measurement
Measurement methodsGrounding resistance: rated current change pole method, test current > 20mA (sine wave), 128Hz;Ground Voltage: Average Rectification
Test frequency128Hz
Display mode4-bit large LCD display, gray screen backlight
Measurement instructionsLED flashing indicator during measurement, LCD countdown display
LCD size108mm×65mm
Instrument sizeL/W/H:277.2mm×227.5mm×153mm
Test line length3 strips:red 15m,yellow10m,green 5m each one
Simple test line2strips:red 1.6m,green 1.6m each one
Auxiliary Grounding rod2PCS:φ10mm×200mm
Measure timeGround voltage:about 2 times/sec; grounding resistance: about 5 seconds/time
Measurement times5000 times or more
Line voltageMeasuring grounding voltage : AC 600V or less
USB interfaceWith USB interface, software monitoring, storage data can be uploaded to the computer, save and print
Communication LineOne USB communication line, 1.5m long
Data storage500 groups, flashing “FULL” symbol indicates that the memory is full
Data reviewData review function: “MR” symbol display
Overflow displayOver-range overflow function: “OL” symbol display
Alarm functionAlarm when the measured value exceeds the alarm setting value
Battery voltageReal-time display of battery power, reminding timely charging when battery voltage is low
Power consumptionBacklight:25mA Max
 Standby: 25mA Max(Backlight off)
 measuring:70mA Max(Backlight off)
WeightInstrument: 2397g(含电池)
 Test lines:861.5g(含简易测试线)
 Auxiliary grounding rod: 425g(2根)
 Instrument bag: 271g
Working temperature and humidity-10℃~40℃;below 80%rh
Storage temperature and humidity-20℃~60℃;below 70%rh
Overload protectionGrounding resistance:AC 280V/3 seconds between E-H and E-S ports
Insulation resistance10MΩ以上(500V between circuit and housing)
Pressure resistanceAC 3700V/rms(between circuit and housing)
Electromagnetic propertiesIEC61010-4-3,Wireless frequency electromagnetic field≤1V/m
Suitable for safety regulationsIEC61010-1、IEC1010-2-31、IEC61557-1,5、IEC60529(IP54)、Pollution level 2、CAT Ⅲ 300V