FR2000+ Series Clamp Earth Resistance Tester

FR2000+ Series Clamp Earth Resistance Tester

  • Resistor Resolution:0.001Ω
  • Current resolution:0.01mA
  • Measurement Method:mutual inductance
  • Data Storage:300 groups, “MEM” storage indication, displaying “FULL” symbol means the storage is full
  • Measure Time:2 times/sec
ModelResistance RangeCurrent Range
FR2000A+0.01Ω-200Ω—
FR2000+0.01Ω- 500Ω—
FR2000C+0.01Ω-1200Ω0.00mA-20A
FR2000B+Explosion-proof0.01Ω-1200Ω 

Technical Parameter

FunctionGround resistance test, loop resistance test, leakage current test
Ambient Temperature and Humidity23℃±5℃, below 75%rh
Power SupplyDC 6V (4 AA dry batteries)
Measurement Methodmutual inductance
Resistor Resolution0.001Ω
*Current resolution0.01mA
Jaw size55mm×32mm
*Ω + A sync displayΩ + A sync display
Ground voltage measurement functionNone
Display Mode4-digit LCD display, black screen design
LCD size46mm×29mm
Meter sizeLength, width and height:285mm×85mm×58mm
Measure Time2 times/sec
Data Storage300 groups, “MEM” storage indication, displaying “FULL” symbol means the storage is full
Data Access“MR” symbol indication when viewing data
Overflow Display“OL” symbol indication when over range overflow
Interference TestAutomatically identify interference signals, and the “NOISE” symbol indicates when the interference current is large
Alarm FunctionWhen the measured value exceeds the alarm setting value, an alarm prompt will be issued
Battery VoltageReal-time display of battery power, reminding to charge in time when the battery voltage is low
Automatic shut-downAutomatic shutdown after 5 minutes of startup
Power consumption50mA Max
QualityMeter: 1180g (including battery)
Working temperature and humidity-10℃~40℃; below 80%rh
Storage temperature and humidity-20℃~60℃; below 70%rh
Insulation resistanceAbove 20MΩ (500V between circuit and case)
Pressure resistanceAC 3700V/rms (between circuit and case)
External Magnetic Field<40A/m
External Electric Field<1V/m
Suitable for safety regulationsIEC61010-1 (CAT III 300V, CAT IV 150V, pollution degree 2);IEC61010-031;IEC61557-1 (grounding resistance);