FR3010 Series Digital Earth Resistance Tester

FR3010 Series Digital Earth Resistance Tester

  • Earthing Resistance Range:0.01Ω~3000Ω Accuracy±1.5%rdg±5dgt
  • Ground resistance resolution: 0.01Ω
  • Grounding voltage range:0.01~600V AC Accuracy±1.5%rdg±3dgt
  • Ground voltage resolution:0.01V
  • Measuring Mode:Precise 3-pole measurement, simple 2-pole measurement

FR3010 Technical Parameter

Earthing Resistance Range0.01Ω~3000Ω Accuracy±1.5%rdg±5dgt
Ground resistance resolution0.01Ω
Grounding voltage range0.01~600V AC Accuracy±1.5%rdg±3dgt
Ground voltage resolution0.01V
Reference conditions23°C±5°C, 75%rh or less (Auxiliary earth resistance 100Ω±5%, voltage to ground <10V)
FunctionEarth ground resistance measurement, voltage to ground measurement, low value resistance measurement
Power SupplyDC 6V 1.5V LR14 battery
BacklightControllable gray screen backlight, suitable for use in dim places 
Measuring ModePrecise 3-pole measurement, simple 2-pole measurement
Measuring MethodEarth ground resistance: rated current change-pole method, Test current >20mA (sine wave),128Hz;Voltage to ground: average value rectification
Wire Resistance VerificationAvoid error caused by testing wire that is failed to be fully inserted into tester interface or by poor contact or by users’ replacing or lengthening testing wires, making it more accurate for earth ground resistance measurement.
Display Mode4-digital super-large LCD display, gray screen backlight
Measuring indicatorDuring measurement, LED flash indicator, LCD count down display
LCD Dimension108mm×65mm
DimensionL×W×H: 240mm×188mm×85mm
Testing WiresThree wires: each for Red 15m, Yellow 10m, and Green 5m
Simple Testing Wire2 wires: each for Red 1.5m and Green 1.5m
Auxiliary earthing rod2 PCS
Measuring RateVoltage to ground: about 2 times/second; earth ground resistance: about 5 seconds/time
Measuring TimesOver 5000 times
Circuit VoltageMeasuring voltage to ground: measuring below AC 600V
Data Storage500 sets, flash display “FULL” icon to indicate storage is full
Data ReadData read function: “MR” icon display
Overflow DisplayExceeding measuring range overflow function: “OL” icon display
Alarm FunctionWhen measuring value exceeds alarm setting value, there is beeper alarming
Battery VoltageBattery power indicate in real time, the battery voltage is low and remind to charge in time
Power ConsumptionBacklight:25mA Max
 Standby: 25mA Max(Backlight shut off)
 Measurement:70mA Max(Backlight shut off)
WeightTester:1230g (including battery)
 Testing Wires:610g (including simply testing wires)
 Auxiliary earthing rod:360g(2 PCS)
 Meter bag:1200g
Working Temperature & Humidity-10℃~40℃;below 80%rh
Storage temperature & humidity-20℃~60℃;below 70%rh
Overload ProtectionMeasuring earth resistance: between each interfaces of E-H、E-S, AC 280V/3 seconds
Insulation ResistanceOver 10MΩ(between circuit and enclosure it is 500V)
Withstanding VoltageAC 3700V/rms (Between circuit and enclosure)
Electromagnetic FeaturesIEC61010-4-3, radio frequency electromagnetic field ≤ 1V/m
Protection TypeIEC61010-1、IEC1010-2-31、IEC61557-1,5、IEC60529(IP54)、Pollution grade 2、CAT Ⅲ 300V

FR3010E Technical Parameter

FunctionTwo, three, four-wire measure grounding resistance, soil resistivity; Ground voltage, AC voltage
Ambient temperature and humidity23℃±5℃,below 75%rh
Power SupplyDC 9V 6-section LR14 Dry Battery Standby for more than 100 hours
Interference voltage<20V(should be avoided)
Interference current<2A (should be avoided)
Measure R electrode spacinga>5d
Measured electrode spacinga>20h
Auxiliary Earth ResistanceReference Conditions <100Ω, Operating Conditions <5kΩ
RangeGrounding resistance: 0.00Ω to 30.00kΩ
 Soil resistivity: 0.00Ωm~9999kΩm
 Ground voltage: 0.00V to 600.0V
Measurement MethodPrecision 4-wire, 3-wire measurement, simple 2-wire grounding resistance
Measuring MethodsGrounding resistance: rated current change methodSoil resistivity: four-pole methodGround voltage: average rectification (S-ES interface)
Test Frequency128Hz
Short-circuit Test CurrentAC >20mA (sine wave)
Open Circuit Test VoltageAC 28V max
Electrode Spacing Rangecan be set from 1m to 100m
Change GearGrounding resistance: fully automatic shifting from 0.00Ω to 30.00kΩ
 Soil resistivity: 0.00 Ωm~9000kΩm automatic shifting
BacklightGray screen backlight, suitable for dim places 
Display Mode4-digital super-large LCD display, blue screen backlight
Measuring IndicatorDuring measurement, LED flash
LCD Frame Dimension111mm×65mm
LCD display area108mm×65mm
DimensionL×W×H: 240mm×188mm×85mm
Standard Test Wire4 wires: each for red 20m, black 20m, yellow 10m, and green 10m
Simple Test Wire2 wires: each for yellow 1.5m and green 1.5m
Auxiliary Earthing Rod4 PCS
Measuring RateVoltage to ground: about 3 times/second
 Earth resistance, soil resistivity: about 7 seconds/time
Circuit Voltagebelow AC 600V(The ground voltage measurement function cannot be used to measure commercial power)
Data Storage500 sets, “MEM” icon storage indicator, flash display “FULL” icon to indicate storage is full
Data ReadData read function: “MR” icon display
Overflow DisplayExceeding measuring range overflow function: “OL” icon display
Alarm FunctionAlarm when the measured value exceeds the alarm setting value
Battery VoltageLow battery voltage symbol display
Automatic Shut-down“APO” instruction, automatically shut down after 15 minutes of power on
Power ConsumptionStandby: About 40mA (backlight off)
 Turn on and backlight on: about 43mA
 Measurement: about 75mA (backlight off)
WeightTester:1230g (including battery)
 Testing Wires:1300g
 Auxiliary earthing rod:720g(4 PCS)
Working Temperature & Humidity-10℃~40℃;below 80%rh
Storage temperature & humidity-20℃~60℃;below 70%rh
Overload ProtectionMeasuring earth ground resistance: between each interfaces of H-E、S-ES, AC 280V/3 seconds
Insulation ResistanceOver 20MΩ(between circuit and enclosure it is 500V)
Withstanding VoltageAC 3700V/rms (Between circuit and enclosure)
Electromagnetic FeaturesIEC61326(EMC)
Protection TypeIEC61010-1 (CAT III 300V, CAT IV 150V, Pollution Degree 2);IEC61010-031;IEC61557-1 (grounding resistance);IEC61557-5 (soil resistivity);JJG 366-2004