ES3030 Digital Large Ground Network Tester

ES3030 Digital Large Ground Network Tester

  • Earth resistance range:0-2000Ω
  • Test frequency:45Hz、55Hz、Automatic dual frequency optional
  • Short circuit test current :1A、2A、3A、4A、5A(5 file settings)
  • Data storage:100 groups, “Save successfully!” Store indication, display “Save failed, space is full!” character indicates that the storage is full
  • Print :Built-in thermal printer
FunctionGround resistance measurement, soil resistivity measurement, step voltage measurement, distributed potential measurement, contact voltage measurement
Ground resistance range0.030~2.000Ω    Accuracy:±2%rdg±5dgt
 0~20.00Ω        Accuracy:±2%rdg±5dgt
 0~200.0Ω        Accuracy:±2%rdg±5dgt
 0~2000Ω        Accuracy:±2%rdg±5dgt
Ground resistance resolution0.001Ω
Rated measuring power2000W
Capacity of resisting disturbanceAnti-power frequency 50hz voltage 50v
Base condition23℃±5℃,below 70%rh   (Auxiliary ground resistance 20Ω±10%,voltage to earth<10V)
PowerAC 220V 10A (50Hz)
BacklightControllable gray screen backlight
Measurement modefour-wire measurement, three-wire measurement, two-wire measurement
Measurement methodGrounding resistance: rated current method
Short circuit test current1A、2A、3A、4A、5A(5 file settings)
Soil resistivity electrode spacing rangeCan set 1m~100m
Test frequency45Hz、55Hz、Automatic dual frequency optional
Short circuit maximum currentAC  5A±10%  Sine wave
No-load maximum voltageAC  400V±10%  Sine wave
Display mode7-inch touch-control color screen
Touch screenyes
Measurement indicationMeasurement progress display, measurement prompt animation display
Instrument sizeL/W/H:540mm*440mm*210mm
Standard test line lengthRed 15m,black 15m,yellow 10m,green 10m,yellow 1.5m,green 1.5m each one
Auxiliary grounding rob800mm 2pcs , 200mm 2pcs
Measurement timeground impedance:about 1min/time
PrintBuilt-in thermal printer
Print paper specification57*40mm
Data storage100 groups, “Save successfully!” Store indication, display “Save failed, space is full!” character indicates that the storage is full
Data reviewyes
Overflow displayOver-range overflow function: “OL” symbol display
Automatic shut-downno
Power consumptionStandby: <110W
 Measure:2000W
WeightInstrument:27kg
 Test line、Auxiliary ground rob、 Instrument bag:5.5kg
Working temperature and humidity-10℃~40℃;Below 80%rh
Storage temperature and humidity-20℃~60℃;Below 70%rh
Insulation resistance10MΩ above(Between circuit and case500V)
Pressure resistanceAC 3700V/rms(Between circuit and case)
Electromagnetic propertiesIEC61010-4-3,Wireless frequency electromagnetic field≤1V/m
Suitable for Safety RegulationsIEC61010-1、IEC1010-2-31、IEC61557-1,5、IEC60529(IP54)、Pollution Degree 2、CAT Ⅲ 300V