ES1010 Wireless H/L Voltage Current Ratio Tester

ES1010 Wireless H/L Voltage Current Ratio Tester

  • High voltage range :0.0mA-1200A
  • Low voltage range : 0.0mA -20A
  • High voltage clamp jaw : 50mm
  • Low coltage clamp jaw : 8mm
  • Shift gear :automatic shift
  • line voltage : below 60KV

Technical Parameter

TesterHigh voltage detectorMainframe (current clamp)
Range0.0mA~1200A(50/60Hz Auto)0.0mA~20A
Resolution0.1mA0.1mA
Jaw sizeφ50mmφ7.5mm
Accuracy±2%±5dgt±0.5%±5dgt
Sampling Rate2 times/second
FunctionHigh-low voltage current transformer primary and secondary loop current, transformation ratio, polarity, phase, and on-line test; current and voltage ratio on both sides of transformer; on-line test; load current test
Transmission typeWireless transmission, linear transmission distance 30m
Change gearFully automatic shift
PowerDC6V 7# alkaline battery(1.5V AAA×4)DC7.5V 5# alkaline battery(1.5V LR6×5)
Test methodClamp CT
DimensionsW/T/H 87*37*262mmHost:W/T/H 100*35*204mm
  Current clamp:W/T/H 42*20*137mm
Display modeLCD:128dots×64dots  Blue screen backlight for dim places
LCD Size62mm×44mm
Change ratioThree kinds of transformation ratio display: (The primary and secondary circuit actually measured the current transformation ratio; the conversion ratio of the secondary circuit 5A; 10kV-YY transformer conversion ratio of 10kV/380V), the maximum ratio of 1:1 million
Line voltageLine test with insulation sheath below 60kV or bare wire current test below 35kV (with insulation rod operation)
Lead lengthCurrent clamp lead 2 meters
WeightTotal instrument weight:7Kg(Insulated rod and instrument package)
 High pressure detector:370g(Including battery)
 Host:409g(Including battery)
 Current clamp:180g
Data interfaceUSB transmission
Overflow displayOver-range overflow function: “OL A” symbol display
Data storage500 groups, press MENU to keep data, HOLD symbol display, press MENU again to cancel
Data reviewLong press the MENU button to enter the data reference mode,  MR symbol display, press MENU again to exit
Data is fullData full function: “FULL” symbol display
Switch display modeLong press the POWER button to switch between the test display mode and the conversion ratio display mode
No signal indicationWhen the host does not receive the transmit signal, it prompts “no signal”
Automatic shut-downAbout 15 minutes after power on, the meter will automatically shut down
Battery voltageWhen the battery voltage drops to 3.5V, the low-power indicator lights to remind you to replace the batteryWhen the battery voltage drops to 5.2V, the battery voltage is low symbol to remind to replace the battery
Insulation rodFive section insulation rod (5 meters)
Insulation strengthAC 60kV/rms
Line testInsulation sheath wire test below 60kV line voltage, bare wire test below 60kV (with insulation rod operation)
Working temperature-10℃~40℃
Storage temperature-10℃~60℃
Relative humidity0℃~31℃≦75%,31℃~40℃≦50%
Suitable for safety regulationsIEC1010-1、IEC1010-2-032、Pollution degree 2、CAT Ⅲ(600V) IEC61326(EMC standard)