FR2010+ Series Double Clamp Digital Phase Voltammeter

FR2010+ Series Double Clamp Digital Phase Voltammeter

  • Voltage range: AC 0.00V~600V
  • Current range: AC 0.0mA~20.0A
  • Phase range:0.0°~360.0°
  • Frequency range:45.00Hz~65.00Hz
  • Detection rate: About 2 seconds/time

Technical Parameter

FunctionMeasure two AC voltages, currents, phase between voltages, phase between currents, phases between voltages and currents, frequencies, determine transformer wiring groups, inductive, capacitive circuits, test secondary loops and busbar protection systems, read out the phase relationship between the CTs of the differential protection groups, check the wiring of the power meter, check the line equipment, etc.
PowerBuilt-in large capacity lithium battery 3.7V
Power consumptionTurn on the backlight and consume up to 50mA. The battery can work continuously for more than 48 hours.
Display modeLCD display,71*52mm
Instrument sizeL/W/T:187*191*51mm
Jaw sizeΦ8mm
Voltage rangeAC 0.00V~600V
Current rangeAC 0.0mA~20.0A
Phase range0.0°~360.0°
Frequency range45.00Hz~65.00Hz
ResolutionVoltage:AC 0.01V
 Current:AC 0.1mA
 Phase:0.1°
 Frequency:0.01Hz
Detection rateAbout 2 seconds/time
Data holdPress HOLD key to hold data during test, “DH” symbol display
Automatic shut-downAbout 15 minutes after power on, the meter will automatically shut down to reduce battery consumption
Backlight functionSuitable for dim places and night use
Voltage detectionFour grids of power are displayed, and the remaining one should be charged in time
Instrument weightHose:473g
 Tip-shaped current clamp:180g×2
 Test line:190g
Test line length1.5m
Line length of the current clamp2m
Working temperature and humidity-10℃~40℃;below 80%Rh
Storage temperature and humidity-10℃~60℃;below 70%Rh
input impedanceTest voltage input impedance is:1MΩ
Pressure resistanceThe withstand voltage of 1000V/50Hz sine wave AC voltage between the instrument circuit and the housing lasts 1 minute
insulationBetween instrument line and housing≥100MΩ
structureDouble insulation
Suitable for safety regulationsIEC61010-1 CAT Ⅲ 600V,IEC61010-031,IEC61326,Pollution level 2